Q: How should the maximum module quantity of 16 be understood?
A: The maximum module quantity refers to the total number of modules connected across all devices. At present, all expansion modules of the S7-200 series can be connected.
F7 288-5AN04-6AA0,4-Channel NTC Thermistor Temperature Acquisition, supporting 10k/3950 thermistors,Configure as SB CM01 during setup.



Power off the PLC before installing or removing the signal board. Hot swapping is not supported.

1. Use a flat-head screwdriver to carefully remove the signal board from the CPU.

2. Press the replacement signal board into the slot onthe PLC CPU module to complete the installation.

Selected high-quality electronic components,imported MCU, and premium gold-plated connectorsensure stable and reliable performance.

Supports configurable filter depth, along with over-limit alarms, wire-break detection, and real-timemodule status monitoring.

Features built-in configuration instructions and ready-to-use sample routines-get started in one minutewith effortless operation.

Built-in overvoltage and overcurrent protection onports ensures reliable operation in various complexand unexpected industrial environments.

The high-speed processor uses oversamplingtechnology to achieve 16-bit high-precision signalacquisition. Combined with advanced filteringalgorithms, it delivers stable, fast, accurate, andreliable signal acquisition.
Supports multiple temperature sensors with adjustable filtering depth, enabling flexible adaptation to a wide range of application scenarios.




| Specification parameters | |
|---|---|
| Model no | SB AN06 |
| Article No | F7 288-5AN06-6AA0 |
| Product Description | 6-Channel NTC Thermistor Temperature Acquisition, supporting 10k/3950 thermistors |
| Compatible Model | SB CM01 |
| Dimensions WXHxD(mm) | 35x52.2x16mm |
| Digital Signal Board | SB DE02 | SB DE04 | SB DE06 | SB DT04 | SB DT06 | SB QT02 | SB QT04 | SB QT06 |
|---|---|---|---|---|---|---|---|---|
| Number of channels | 2 inputs | 4 inputs | 6 inputs | 2 inputs / 2 outputs | 4 inputs / 2 outputs | 2 outputs | 4 outputs | 6 outputs |
| Digital input type | Sink type or source type (supports bidirectional input, common terminal can be connected to positive or negative) | |||||||
| Digital input voltage |
Logic 1 minimum: 2.5mA at 15VDC; Logic 0 maximum: 1mA at 5VDC. |
|||||||
| Digital input isolation | Internal optocoupler isolation | |||||||
| Digital output type | Source type | |||||||
| Maximum output current | 0.5A | |||||||
| Digital output isolation | Internal optocoupler isolation | |||||||
| L+, M rated voltage | 24VDC (maximum 30VDC) | |||||||
| Analog Input Specifications | SB AE02 | SB AE04 | SB AE06 | SB AM03 | SB AM06 |
| Number of inputs | 2 voltage/current inputs | 4 voltage/current inputs | 6voltage/current inputs | 4 voltage/current inputs | |
| Measurement range | -10V10V, -20mA-20mA | ||||
| Full-scale range | -27647~27648 | ||||
| Accuracy | ±1% of full scale | ||||
| Isolation | None | ||||
| Analog Output Specifications | SB AM03 | SB AM06 | SB AQ02 | SB AQ04 |
| Number of inputs | 1 current or voltage output | 2 current or voltage outputs | 4 current or voltage outputs | |
| Resolution | Voltage: 11 bits + sign bit; Current: 11 bits | |||
| Full-scale range (digital data) | 0 to 27,648 corresponding to 0–10V and 0–20mA | |||
| Accuracy | ±1% of full scale | |||
| Load impedance | Voltage: ≥1000Ω; Current: ≤600Ω | |||
| Isolation | None | |||
| Maximum cable | 10m shielded twisted pair cable | |||
| Temperature Signal Board | SB AR02 | SB AR04 | SB AN04 | SB AN06 | SB AT04 |
| Number of inputs | 2 channels | 4 channels | 4 channels | 6 channels | 4 channels |
| Sensor type | See resistance temperature sensor selection table | NTC (10K,3950) | See thermocouple selection table | ||
| Measurement range | -50.0°C~150.0°C | ||||
| Reading range | -500~1500 | ||||
| Resolution | (×10 amplification) 0.1°C | ||||
| Accuracy | ±0.5% of full scale | ||||
| Wire break / overrange detection | Yes | ||||
| Sampling time | 200ms | 400ms | 200ms | 400ms | |
| Maximum cable length | Maximum 100m | Maximum 30m | Maximum 20m | ||
| Communication Board Technical Parameters | SB CM01 | SB CM01_R485 | SB CM01_R485 | SB CM01_i485 |
| Cable length | 1000m | |||
| Isolation | None | Yes | ||
| ESD protection | Yes | |||